Contractor Glossary · Electrical
Conduit Body: The Types, the Volume, and the Splice Rule
Most crews believe any conduit body can hold a splice. The permission is conditional, and the condition is cast into the body.
Pricing the conduit run? Estimate it from a photo.

What is a conduit body?
A conduit body is a fitting that opens a raceway. NEC Article 100 defines it as a separate portion of a conduit or tubing system that provides access through a removable cover to the interior, at a junction of two or more sections or at a terminal point. It is part of the pipe, not a box on it.
SimplyWise Cost Estimator turns a photo of the work into an itemized estimate in about 6 seconds.
Why it is not a box
The same definition adds that FS and FD boxes, and larger cast and sheet metal boxes, are not conduit bodies. An outlet box mounts to structure and holds a device. A junction box holds splices. A conduit body does either only when it is built and marked for it.
What Article 314 actually requires
Three rules govern. The splice rule is the one crews get wrong.
Splices: 314.16(C)(2) is conditional
Only conduit bodies the manufacturer durably and legibly marked with their cubic inch capacity may contain splices, taps or devices. The count is then figured the same way as fill in any other nonstandard box. No marking, no splice.
Pass through: 314.16(C)(1) sizes the body against the pipe
Any conduit body enclosing 6 AWG or smaller, other than a short radius type, needs a cross sectional area at least twice that of the largest conduit it attaches to, splices included. With no splice, the count is whatever that conduit may carry. Short radius bodies, capped elbows and service entrance elbows get 314.16(C)(3). No splices, taps or devices.
Pulling room: 314.28 starts at 4 AWG
At 4 AWG and larger insulated conductors the dimensional rules switch on. A straight pull needs a body at least eight times the trade size of the largest raceway. An angle pull, a U pull or a splice needs six times that from each entry to the opposite wall, unless that wall is the removable cover. Add the diameters of the other entries in that row. Under 314.28(A)(3) a listed body may be smaller.
A worked example, 12 AWG in a 3/4 inch LB
Table 314.16(B)(1) gives 12 AWG a volume allowance of 2.25 cubic inches each.
- Splice a two wire circuit: hot in, hot out, neutral in, neutral out. 4 x 2.25 = 9.00.
- The grounds together take one allowance, another 2.25. Total 11.25 cubic inches.
- Southwire Form 7 Type LB, 3/4 inch, part LB2G7: internal volume 5.8. No.
- Appleton Form 85 Type LB, 3/4 inch: 7.00 body plus a 0.80 cover, so 7.80. No.
- Step to 1 inch. Southwire LB3G7 is 9, still short. Appleton Form 85 is 11.80 body plus a 0.50 cast cover, so 12.30.
Appleton’s table is headed combine body and cover capacities for total usable capacity per 314.16(A). Its iron FM7 at 1 inch reads 11.00 in the body and 1.30 in the cover, so 12.30 as well. Read the body capacity alone and you will condemn a body that is legal. Read both markings on the parts in your hand.
The letters, in plain language
| Letter | What it does at the corner |
|---|---|
| LB | Turns the run 90 degrees out the back, opposite the cover. Where a run leaves a wall and drops. |
| LL | Same turn, out the left side of the body. |
| LR | Same turn, out the right side. |
| C | Straight through. A pull point in a long run. |
| T | Three hubs. A branch leaves the run. |
| X | Four hubs. Two runs cross. |
LB, LL, LR, C, T and X is the common set. IAEI describes the two hub bodies as straight, LB, LL or LR, three hub bodies as T and four hub bodies as X. The second letter marks where the run is diverted, not where the cover sits.
Where it shows up on a job
On the takeoff
Count bodies per corner and pull point. Our electrical estimate template keeps them off the fittings lump.
At inspection
The inspector looks for the volume marking first.
Common mistakes
Splicing in an unmarked body
The marking is the permission. Plenty of listed bodies carry no capacity marking, because they were never meant to hold a splice.
Sizing off the hub
Hub size and internal volume do not track across makers.
Price the conduit run, not just the fittings
SimplyWise Cost Estimator turns a photo into an itemized estimate in about 6 seconds, with material and labor lines you can edit. Pricing is $29.99/mo or $239.99/yr, about $20/mo on annual, with a 7-day free trial.
Pick a conduit body in four steps
-
Decide whether anything gets spliced
No splice, tap or device means 314.16(C)(1) governs and the pipe sets the count.
-
Read the cubic inch marking
If you are splicing and there is no legible manufacturer capacity on the casting, the body is out.
-
Add the box fill
Count each conductor once at its Table 314.16(B)(1) allowance, one allowance for four grounds or fewer, a quarter each beyond.
-
Check 314.28 if anything is 4 AWG or larger
Eight times the trade size for a straight pull, six for an angle pull, unless listed smaller.
Keep reading
Sources
Code text
- Adopted text, E3905.12.3 (bracketed to 314.16(C); 2026-09-14).
- Adopted text, Table E3905.12.2.1 (Table 314.16(B)(1); 2026-09-14).
- 314.28(A)(1) straight pulls (2026-09-14).
- IAEI, conduit bodies and the NEC (2026-09-14).
Manufacturer catalogues
- Southwire conduit bodies catalogue (2026-09-14).
- Appleton Form 85 conduit outlet bodies (2026-09-14).
Product
- SimplyWise Cost Estimator (2026-09-09).
Common questions about conduit bodies
What counts as one
What is a conduit body?
A separate portion of a conduit or tubing system that gives access through a removable cover to the inside of the system, at a junction of two or more sections or at a terminal point.
What is a condulet?
Trade shorthand for the same fitting. Condulet began as a brand name, and crews use it for any LB, LL, LR, C, T or X body.
Splices and sizing
Can you splice inside a conduit body?
Only in one the manufacturer durably and legibly marked with its cubic inch capacity, and only if the box fill fits inside that number. No marking means no splice.
How many 12 AWG conductors fit in a conduit body?
Divide the marked body and cover capacity by 2.25 cubic inches. A 3/4 inch LB at 7.80 holds three. Splicing a two wire circuit with grounds needs 11.25.
What is the 6 and 8 times rule?
It is 314.28, and it starts at 4 AWG. Eight times the largest trade size for a straight pull, six times from each entry to the opposite wall for an angle pull.
Turn the conduit run into a signed quote.
Snap a photo and get an itemized estimate in about 6 seconds. Free to try.